Potter IntelliView™ Troubleshooting


IntelliGen™ Nitrogen Generator


Excessive Membrane Run Time

Issue: Nitrogen Valves continuously ON for 2 hours.

Probable Cause:

  1. Air compressor power is turned off.
  2. Ball valve from air tank to nitrogen generator closed.
  3. Blockage in pathway from air tank to nitrogen tank.
  4. Pneumatic inlet or outlet valves are closed.
  5. Instrument air pressure regulator is less than 40 PSI.